Assessment of hygienic status of central air conditioning ventilation system in public places by fuzzy comprehensive evaluation method
- VernacularTitle:公共场所集中空调通风系统卫生质量的模糊综合评价
- Author:
Qiang CHEN
1
;
Zuo-Yi WANG
;
Shu-Hua QIU
;
Xiao-Qing HE
Author Information
1. 金华市疾病预防控制中心
- Keywords:
Central air conditioning ventilation system;
Fuzzy comprehensive evaluation;
Hygiene quality
- From:
Journal of Preventive Medicine
2015;(5):436-439
- CountryChina
- Language:Chinese
-
Abstract:
Objective To assess the hygienic status of the central air conditioning ventilation system in public places by fuzzy comprehensive evaluation method.Methods According to the comprehensive evaluation method of public place (WS /T 199—2001),a fuzzy comprehensive evaluation method was applied to evaluate central air conditioning ventilation systems in 15 large public places of Jinhua City.Results The qualified rate of central air ventilation system was 53.30%, and the qualified rates of total number of bacteria,the fungi,β-hemolytic streptococcus in air blow and Legionella bacteria in the cooling water all reached 100.00%.At the same time,the qualified rate of bacteria,fungi and dust volume in internal surface of pipe were 93.33%,86.67% and 80.00% respectively.The qualified rate of PM10 was 86.67%. Among 15 central air conditioning ventilation systems,13 systems were evaluated as level Ⅰ,and the other two was as level Ⅱand Ⅳ respectively.TAAlso,14 evaluated units got the fuzzy comprehensive indexes of central air ventilation less than 0.5.Conclusion The hygiene status of central air conditioning ventilation system in Jinhua is acceptable,and the management of hygiene quality should be strengthened.