Problems With Medical Gas Fitting in Great Earthquake Disaster
10.2185/jjrm.61.710
- VernacularTitle:大震災における医療ガス設備の問題点
- Author:
Yasuji TAKANO
;
Shuzo SHINTANI
- Publication Type:Journal Article
- From:Journal of the Japanese Association of Rural Medicine
2013;61(5):710-714
- CountryJapan
- Language:Japanese
-
Abstract:
The water supply system in our hospital was disabled as its elevated water tank was badly damaged by the earthquake that hit northeast Japan on March11, 2011. Subsequently, the dysfunction of suction equipment of a water seal type threw the whole hospital into utter confusion, though temporarily. We realized that injection of some degree of water could recover the suction system on manual. To minimize the damage from a natural disaster and strengthen the hospital ability for all contingencies, we have decided to employ the oil rotary type rather than the water seal type in the system of suction equipment.