Development of ventilation system for enhanced mobile biosafety level-2 laboratory
10.19745/j.1003-8868.2024127
- VernacularTitle:加强型移动生物安全二级实验室通风系统研究
- Author:
Jian-Qiao XIA
1
;
Kang OU-YANG
;
Hai-Yang LI
Author Information
1. 镇江康飞汽车制造股份有限公司,江苏镇江 212132
- Keywords:
enhaned mobile biosafety level-2 laboratory;
mobile biosafety level-2 laboratory;
ventilation system;
air supply angle;
biosafety
- From:
Chinese Medical Equipment Journal
2024;45(7):29-34
- CountryChina
- Language:Chinese
-
Abstract:
Objective To develop a ventilation system for the enhaned mobile biosafety level-2(BSL-2)laboratory to control the dispersed aerosol within the laboratory effectively.Methods A ventilation system for the enhanced mobile biosafety level-2 laboratory was designed with the concept of full fresh air ventilation,which realized air supply with 3-stage filtration and constant air volume control,and air exhaust with 1-stage high-efficiency filtration and variable air volume control.The buffer room had the layout of upside air supply and upside exhaust,with the air supply and exhaust equipment integrated into the ceiling;the experimental room had the layout of diagonally upside air supply and diagonally downside exhaust.Computa-tional fluid dynamics(CFD)software was used to analyze the airflow organization,temperature field and velocity field at 0°,30°,45°,60° and 90° air supply angles in order to verify the feasibility of the ventilation system design,and the distributions of aerosol concentration in the experimental room at different air supply angles were simulated to determine the optimal air supply angle.Results Investigations in terms of airflow organization,temperature field,velocity field and aerosol dispersion control showed in case of 60° air supply angel the enhanced mobile BSL-2 laboratory behaved the best and its core indexes all met the requirements of GB 27421-2015 Mobile laboratories—Generalrequirements for biosafety and T/CESC 662-2020 Architectural technical standard for BSL-2 laboratory in medical facilities including the number of air changes,static pressure difference,temperature and humidity,cleanliness and airflow direction.Conclusion Considerations have to be taken on the locations of supply and exhaust outlets,the facility layout and air supply angle when the enhanced mobile BSL-2 laboratory is designed so as to enhance the biosafety of the protective area.[Chinese Medical Equipment Journal,2024,45(7):29-34]